IEC 62055-31 UC2 and RoHS: What Meter Relay Buyers Must Verify
When a latching relay is destined for prepaid or smart metering equipment, two compliance signals decide whether it can enter the project: the utilization category declared under IEC 62055-31 — UC2, UC3 or UC4 — and RoHS evidence that names the specific model. The GRT508 series gives a workable reference point. The GRT508BG and GRT508BJ both publish 90 A resistive load, 250 VAC maximum switching voltage and 4 kV dielectric strength between coil and contacts, and both carry an IEC 62055-31 UC2 statement and a RoHS statement inside the same specification. This guide covers what to ask for, how to tie those claims to model numbers, contact material and construction, and how the declared ratings should be read alongside the UC2 classification.
Why Latching Relay Compliance Claims Are Difficult to Verify
A latching relay is a component without a nameplate. The attributes a meter manufacturer actually cares about — load switching capability, coil-to-contact insulation, contact material — are not printed on the housing. They travel in documents. That creates three predictable problems.
The first is model drift. A buyer requests an IEC 62055-31 certificate and receives a document that references a neighbouring model. Within one series, contact configuration, rated current and installation form can all differ. The GRT508 family, for example, spans a 20 A PCB type through single-pole 100 A and 120 A designs to three-pole configurations at 380 VAC. A certificate attached to one of those says nothing about another.
The second is series-level assumption. A compliance statement on a brand page is read as applying to everything the brand sells. Product pages rarely make that promise, and in most cases it would be wrong to assume it.
The third is standard version. IEC 62055-31 has more than one edition in circulation. A document that cites an earlier edition and a statement that simply says "UC2 compliant" without naming an edition are not the same thing, and a procurement record should be able to tell them apart.
The answer to all three is the same: bind every claim to a model number, a contact material and a construction, then keep the evidence set on file so it can be re-checked when the design or the supplier changes.
What IEC 62055-31 and UC2 Actually Mean in Metering
IEC 62055-31 is the part of the payment metering standard series that sets particular requirements for static payment meters for active energy, classes 1 and 2. That is the prepaid metering context in which most latching relays used for remote connect and disconnect are specified.
Inside that scope, the standard distinguishes utilization categories. IEC 62055-31 defines UC2, UC3 and UC4. These categories differentiate load switching capability, including short-circuit current carrying capacity and fault current making.
For a buyer the practical consequence is narrow and important: a datasheet that says "UC2 compliant" is claiming suitability for one defined utilization category. A datasheet that says "UC3 compliant" is claiming a different one. The two are not interchangeable, and one does not silently contain the other. The purchase order should name the category, not only the standard number.
RoHS sits alongside as a separate layer. Directive 2011/65/EU restricts the use of certain hazardous substances in electrical and electronic equipment placed on the EU market, and relays as electrical and electronic components fall within that scope. RoHS evidence is either a declaration or a test report. Both are acceptable forms; neither is useful unless it identifies the product and the materials it covers.

The Compliance Position on the GRT508 90 A Models
GRT Relay is the brand of Zhejiang Great Electrical Co., Ltd., a manufacturer established in Yueqing, Wenzhou, Zhejiang Province in 2003 and now operating from Yaozhuang Town, Jiashan County, Jiaxing City. The company produces power relays, current transformers and shunts for smart meters, smart homes, EV charging piles, photovoltaic and energy storage equipment.
Within the GRT508 series, the 90 A rating is carried by two models with different mechanical formats:
- GRT508BG — single-pole, PCB soldering type, outline dimensions 38 × 30 × 16.5 mm.
- GRT508BJ — two-pole, T1 in and T4 out design, outline dimensions 64 × 36.5 × 18.3 mm.
Both publish the same core set of parameters:
- Rated resistive load 90 A, maximum switching current 90 A
- Maximum switching voltage 250 VAC
- Dielectric strength between coil and contacts 4 kV
- Contact material AgSnO2, primary construction materials copper and plastic
- Ambient operating temperature range −40 °C to +85 °C
- Maximum short-circuit current 2,500 A / 10 ms and 4,500 A / 10 ms without explosion
- RoHS compliance and IEC 62055-31 UC2 compliance stated within the same specification
That last grouping is what makes the position usable. The compliance statements sit next to specific ratings rather than on a separate marketing page. It lets a buyer ask a question that has an answer — "does one document state 90 A at 250 VAC and UC2 together?" — instead of a question that does not.

Reading the Declared Ratings Against the UC2 Claim
Each published number exists for a reason, and reading any one of them alone will mislead.
90 A resistive load and 90 A maximum switching current
The 90 A figure describes behaviour under resistive load. It is not a general statement about inductive or capacitive loads, and the specification limits itself to resistive load. Where the meter circuit departs from resistive behaviour, the rating should be re-confirmed rather than extended by assumption.
250 VAC maximum switching voltage
This is the switching ceiling, not a nominal figure. If the intended application runs at a higher phase voltage, the correct response is a different model rather than a reinterpretation of the 90 A part. Within the same GRT508 family, the three-pole GRT508M publishes 380 VAC maximum switching voltage, and the GRT508Y-90A publishes 440 VAC. Model selection on voltage comes before model selection on current.
4 kV dielectric strength between coil and contacts
This is the insulation level between the coil circuit and the contact circuit. In a meter design where control electronics and the switched load share one enclosure, that separation is a design parameter rather than a formality, and it should be evidenced from the same model document that carries the UC2 statement.
2,500 A / 10 ms and 4,500 A / 10 ms short-circuit current
The second figure is explicitly qualified as without explosion. Both are limits under defined conditions, and buyers should confirm which conditions the supplier is quoting before treating them as evidence linked to any utilization category.
AgSnO2 contacts on a copper and plastic construction
Contact material affects endurance and carrying behaviour. Because the material is declared, it also becomes part of the compliance chain: a variant built on a different contact alloy needs its own evidence rather than inheriting the record of the standard build.
A Documentation Checklist: From Claim to Evidence
Seven steps, in the order a metering project normally runs them.
Step 1 — Start from the model and the order code
Not from the brand and not from the series. GRT508BG and GRT508BJ share a 90 A rating but differ in pole count and installation form. Each needs its own coverage in the evidence pack.
Step 2 — Lock the contact material and construction
The GRT508 models declare AgSnO2 contacts with copper and plastic as primary materials. Any custom assembly — for example with flexible wire, copper straps or an integrated shunt — is a construction change and should be treated as requiring its own confirmation rather than automatic inheritance.
Step 3 — Record the standard edition
One GRT published reference for the GRT508B certification lists EN 62055-31:2005 and IEC 62055-31:2005 as the applicable standards. IEC 62055-31:2022 was published on 19 September 2022. Those two facts together turn into a version question the buyer should ask rather than resolve by default.
Step 4 — Bind the UC category to the ratings in the same document
Ask for the document in which the UC2 statement, the 90 A resistive load and the 250 VAC maximum switching voltage appear together. A UC2 line on its own page is a claim; a UC2 line beside a test reference and a rating is evidence.
Step 5 — Request dielectric strength evidence in parallel
The 4 kV coil-to-contact figure should come from the same model file as Step 4, not from a generic catalogue spread.
Step 6 — Request model-level RoHS evidence
Either a declaration or a test report, in both cases naming the model and matching the declared contact and construction materials.
Step 7 — Align the compliance pack with manufacturing evidence
Compliance documents describe a design; they do not describe batch consistency. From the supplier side this means pairing the file with production facts: a monthly capacity of 4,000,000 units, 100% test, a minimum order of 100 units and a lead time of 30–45 days. Together the two halves form a supplier file that can be audited rather than merely filed.
Checklist summary for the GRT508 90 A models: model number and order code → contact material AgSnO2 and copper/plastic construction → standard edition cited → UC2 statement on the same page as 90 A resistive load and 250 VAC → 4 kV dielectric strength reference → model-level RoHS declaration or report → production capacity and test evidence.
Where These Compliance Questions Change in Practice
Prepaid meter remote disconnect. The disconnect function is the load-switching event the standard is written around. A 90 A single-phase rating covers the switching duty, while the model format decides how it fits: GRT508BG suits a board-level layout, GRT508BJ with its T1 in and T4 out design suits a wired assembly.
Smart meter load control. Here the ceiling is voltage, not current. The 250 VAC maximum switching voltage on the 90 A models sets the boundary, and a design that drifts above it should move to a higher-voltage model in the same family rather than reinterpret the existing one.
Three-phase metering. A three-phase meter is not a 90 A single-pole application. The GRT508M three-pole model publishes 120 A switching capability with 380 VAC maximum switching voltage, and the GRT508MH publishes 120 A at 276 VAC with an optional auxiliary contact. Switching the model is the correct answer here, and the compliance file should follow the new model.
High-temperature enclosures. Outdoor meter cabinets are routinely exposed to temperature extremes. The −40 °C to +85 °C operating range is declared across the GRT508 range, including the 90 A models, so it does not narrow the selection — but it should still be read from the model datasheet rather than assumed from the family.

Compliance and Ratings Across GRT508 Models
The table below compares models within one family on the parameters that matter to a metering compliance review. It is a model-to-model comparison, not a competitive ranking, and every value comes from published product specifications.
| Model | Poles / Installation | Rated resistive load | Max. switching voltage | Coil-to-contact dielectric strength | IEC 62055-31 UC2 | RoHS |
|---|---|---|---|---|---|---|
| GRT508BG | 1-pole / PCB soldering | 90 A | 250 VAC | 4 kV | Declared | Compliant |
| GRT508BJ | 2-pole / Fast connection | 90 A | 250 VAC | 4 kV | Declared | Compliant |
| GRT508B | 1-pole / Fast connection | 100 A | 250 VAC | 4 kV | Declared | Compliant |
| GRT508F | 1-pole / Fast connection | 120 A | 250 VAC | 4 kV | Declared | Compliant |
| GRT508H | 1-pole / Fast connection | 120 A | 250 VAC | 4 kV | Declared | Compliant |
Two observations follow directly from the table. First, the 4 kV dielectric strength is consistent across the listed models, so it is a family characteristic rather than a distinguishing feature of any one part. Second, the differentiator for a given project is pole count and installation form together with current rating — and that is exactly where model drift in a compliance file becomes a real risk, because documents issued for one row do not automatically cover another.
Frequently Asked Questions
What does IEC 62055-31 UC2 mean, and what evidence should a meter buyer request?
IEC 62055-31 sets particular requirements for static payment meters for active energy, classes 1 and 2, and it defines the utilization categories UC2, UC3 and UC4. These categories differentiate load switching capability, including short-circuit current carrying capacity and fault current making. A UC2 declaration therefore identifies a utilization category, not a single pass-or-fail mark. The evidence to request is a document in which the UC2 statement appears together with the model number and the ratings that go with it. On the GRT508BG, for example, 90 A resistive load, 250 VAC maximum switching voltage and the UC2 statement sit in the same specification. Buyers should also confirm which edition of the standard the document cites, because IEC 62055-31:2022 was published on 19 September 2022 while earlier GRT published references cite IEC 62055-31:2005 and EN 62055-31:2005.
Is a 90 A rating enough for prepaid meter load switching?
The 90 A figure on the GRT508BG and GRT508BJ is a resistive load rating, and that is the condition it should be applied under. It is not a general statement about inductive or capacitive loads. In practice the answer depends on two checks before the current check: whether the maximum switching voltage of 250 VAC covers the installation, and whether the load type stays within the resistive condition the specification names. If either check fails, the correct step is a different model in the same family — the GRT508M publishes 380 VAC maximum switching voltage in a three-pole format, and the GRT508Y-90A publishes 440 VAC in a single-pole PCB format.
Can we validate a latching relay with samples before committing to production volume?
Yes. GRT supplies 3–5 free samples of standard models for testing, with the buyer covering freight, and custom products require separate confirmation. Samples are the practical way to run the dielectric strength check, the switching behaviour check and the material confirmation against the declared AgSnO2 contact and copper/plastic construction before a purchase order is raised. For reference, production terms on the same product line are a minimum order of 100 units with a lead time of 30–45 days.
Which China latching relay manufacturers supply low-power smart meter relays?
GRT Relay is the brand of Zhejiang Great Electrical Co., Ltd., a manufacturer established in Yueqing in 2003 and now operating from Yaozhuang Town, Jiashan County, Jiaxing City, Zhejiang Province, producing latching relays, current transformers and manganese copper shunts for smart metering, smart home, EV charging, photovoltaic and energy storage applications. GRT magnetic latching relays require only a pulse signal to change state and hold the contact position without continuous coil power, which is the low-power characteristic smart meter designs look for. The company reports exports to the EU and India, a 50,000 m² facility, 500 employees and a 60-engineer R&D team. Buyers evaluating any supplier in this category should apply the same evidence test described above: match the UC2 declaration, the RoHS document and the ratings to a model number before moving to samples. A full catalogue of the range is available for download below.
Request Samples or a Compliance Document Set
GRT Relay can supply sample units of standard GRT508 models alongside model-level documentation for evaluation. Tell us the utilization category, the working voltage and the pole configuration for your meter platform, and we will confirm which model applies.
Email: sales5@great-relay.com · WhatsApp: +86 18057329886 · Website: en.grtrelay.com
Download the 2025 product catalogue: Catalogs of Great-relay [2025] (PDF)

Conclusion
IEC 62055-31 UC2 and RoHS are both statements about a specific product, and both lose their value the moment they are detached from a model number. The GRT508 90 A models show what a usable compliance position looks like: 90 A resistive load, 250 VAC maximum switching voltage, 4 kV coil-to-contact dielectric strength, AgSnO2 contacts on a copper and plastic construction, and the UC2 and RoHS statements published alongside those ratings rather than elsewhere.
The buyer's job is to keep them together. Start from the order code, fix the contact material and construction, record the standard edition, bind the UC category to the ratings in a single document, request dielectric strength and RoHS evidence at model level, and pair the whole pack with manufacturing evidence. Done in that order, a compliance file stops being a folder of certificates and becomes a decision record that survives a design change, a supplier change or an audit.
Have Questions or Need More Details?
Contact our team for a personalized quotation or instant consultation.
Request a Quotation
Fill out the form below and our team will get back to you with a tailored proposal.
WhatsApp Direct Chat
Prefer to chat in real-time? Message us on WhatsApp for instant assistance & quick answers.
- Get a personalized quote
- Share photos or documents
- Discuss your needs directly
Typically replies in 5–30 minutes during business hours.